Minimizing the exposure of airborne pathogens by upper-room ultraviolet germicidal irradiation: an experimental and numerical study

Y. Yang, W. Y. Chan, C. L. Wu, R. Y. C. Kong, A. C. K. Lai*

*Corresponding author for this work

Research output: Contribution to journalJournal articlepeer-review

27 Citations (Scopus)

Abstract

There has been increasing interest in the use of upper-room ultraviolet germicidal irradiation (UVGI) because of its proven effectiveness in disinfecting airborne pathogens. An improved drift flux mathematical model is developed for optimizing the design of indoor upper-room UVGI systems by predicting the distribution and inactivation of bioaerosols in a ventilation room equipped with a UVGI system. The model takes into account several bacteria removal mechanisms such as convection, turbulent diffusion, deposition and UV inactivation. Before applying the model, the natural die-off rate and susceptibility constants of bioaerosols were measured experimentally. Two bacteria aerosols, Escherichia coli and Serratia marcescens, were tested for this purpose. It was found out that the general decay trend of the bioaerosol concentration predicted by the numerical model agrees well with the experimental measurements. The modelling results agree better with experimental observations for the case when the UVGI inactivation mechanism dominates at the upper-room region than for the case without UVGI. The numerical results also illustrate that the spatial distribution of airborne bacteria was influenced by both air-flow pattern and irradiance distribution. In addition to predicting the local variation of concentration, the model assesses the overall performance of an upper-room UVGI system. This model has great potential for optimizing the design of indoor an upper-room UVGI systems.
Original languageEnglish
Pages (from-to)3184-3195
Number of pages12
JournalJournal of the Royal Society Interface
Volume9
Issue number77
DOIs
Publication statusPublished - 7 Dec 2012

User-Defined Keywords

  • ultraviolet germicidal irradiation
  • ventilation
  • air disinfection
  • CFD

Fingerprint

Dive into the research topics of 'Minimizing the exposure of airborne pathogens by upper-room ultraviolet germicidal irradiation: an experimental and numerical study'. Together they form a unique fingerprint.

Cite this